(1) Independent lightning protection grounding resistance is≤ 10Ω.
(2) Independent safety protection grounding resistance should be less than or equal to 4Ω.
(3) Independent AC grounding resistance is ≤ 4Ω.
(4) Independent DC grounding resistance is ≤ 4Ω.
(5) Anti-static grounding resistance is generally required as ≤ 100Ω.
(6) Public grounding body (combined grounding) grounding resistance shall not be greater than 1 Ohm.
(7) Traction substation main grounding network grounding resistance should not be greater than 0.5Ω. Independent lightning rod grounding should be separated from the main grounding network, and the groudning resistance of the grounding resistance test meter is not greater than 10Ω.
(1) When the sensitivity of the vibrating mirror is too high, the potential probe can be inserted into the shallow soil. When the sensitivity of the oscillator is not enough, you can inject water along the potential probe and current probe. When the earth interference signal is strong, you can change the speed of the hand crank generator to improve the anti-interference ability and obtain stable readings.
(2) When the distance between the grounding pole e' and the current probe C' is greater than 40m, the position of the potential probe P' can be inserted a few meters from the middle line of E'C', and the measurement error can be ignored. When the distance between the grounding pole e' and the current probe C' is less than 40m, the position of the potential probe P' can be inserted into the middle of the straight line between E' and C'.
(3) In measurement, grounding resistance test meter should be placed smoothly. When shaking the handle, the instrument should be pressed so as not to cause strong artificial shaking, so as not to mistakenly believe that the pointer can not be adjusted to the zero center line.
(4) To ensure the reliability of the measurement results, it is necessary to move the position of the two probes after one measurement and repeat the measurement in the other direction. Generally, each time the measured resistance value is not exactly the same, you can take the average of multiple measurements as the final value.
(5) Prohibit the measurement when there is lightning or the object under test is charged. Grounding resistance test meter prohibit open circuit test, when not in use should be the terminal with bare wire short.
(6) The instrument should be handled and used carefully and gently, to avoid violent vibration.
(7) After each measurement, the probe should be wiped clean after pulling out, and organize the wire for the next use. Store the grounding resistance test meter in a dry, light-proof and vibration-free place.
Techwin grounding resistance test meter is specially designed for online monitoring of the grounding network resistance of lightning protection devices. It can be installed individually or assembled into a wired network and wireless network system. It can be used for wired or wireless communication. It can be externally powered or equipped with solar power. It is equipped with a standard RS485 interface for data communication and can provide a custom programming interface for customers to interface with other private protocols.
Is Surge Backup Protector the Same As Surge Protector?March 13, 20231.The Role of Surge Backup ProtectorBefore the advent of surge backup protectors, the backup protection devices of SPD surge protectors typically used fuses or circuit breakers to separate the short-c...view
The Difference Between Surge Protector and Air SwitchJuly 8, 2022Air switches and surge protectors are usually installed in the distribution box of a building, so what is the difference between them? Tiandun Thunderbolt will do a detailed analysis for you.Ⅰ. Surge...view
Selection Principle of Surge Protector in Distribution BoxJune 20, 2022(1) The voltage protection level Up of SPD should always be less than the impulse withstand voltage Uc of the protected equipment, and greater than the maximum operating voltage Us of the power grid o...view
The main measures for preventing direct lightning strikes on low-voltage overhead transmission linesSeptember 29, 2025I. Core Measure: Installation of Overhead Ground Wires (Shield Wires)This is the most effective and fundamental direct lightning protection measure, particularly suitable for lightning-proneareas or c...view
The imortant technical characteristics of SPDSeptember 8, 2021Maximum continuous operating voltage UCThe maximum continuous operating voltage (old: rated voltage) is the maximum root mean square value (rms) of the allowable voltage applied to both ends of the su...view
Antenna Surge Protective Device for Cellular Base StationsJuly 3, 2024Currently, the world is experiencing significant changes, including planning and establishing new mobile radio sites, as well as revitalizing and expanding existing network infrastructure. In the era ...view