(1) Independent lightning protection grounding resistance is≤ 10Ω.
(2) Independent safety protection grounding resistance should be less than or equal to 4Ω.
(3) Independent AC grounding resistance is ≤ 4Ω.
(4) Independent DC grounding resistance is ≤ 4Ω.
(5) Anti-static grounding resistance is generally required as ≤ 100Ω.
(6) Public grounding body (combined grounding) grounding resistance shall not be greater than 1 Ohm.
(7) Traction substation main grounding network grounding resistance should not be greater than 0.5Ω. Independent lightning rod grounding should be separated from the main grounding network, and the groudning resistance of the grounding resistance test meter is not greater than 10Ω.
(1) When the sensitivity of the vibrating mirror is too high, the potential probe can be inserted into the shallow soil. When the sensitivity of the oscillator is not enough, you can inject water along the potential probe and current probe. When the earth interference signal is strong, you can change the speed of the hand crank generator to improve the anti-interference ability and obtain stable readings.
(2) When the distance between the grounding pole e' and the current probe C' is greater than 40m, the position of the potential probe P' can be inserted a few meters from the middle line of E'C', and the measurement error can be ignored. When the distance between the grounding pole e' and the current probe C' is less than 40m, the position of the potential probe P' can be inserted into the middle of the straight line between E' and C'.
(3) In measurement, grounding resistance test meter should be placed smoothly. When shaking the handle, the instrument should be pressed so as not to cause strong artificial shaking, so as not to mistakenly believe that the pointer can not be adjusted to the zero center line.
(4) To ensure the reliability of the measurement results, it is necessary to move the position of the two probes after one measurement and repeat the measurement in the other direction. Generally, each time the measured resistance value is not exactly the same, you can take the average of multiple measurements as the final value.
(5) Prohibit the measurement when there is lightning or the object under test is charged. Grounding resistance test meter prohibit open circuit test, when not in use should be the terminal with bare wire short.
(6) The instrument should be handled and used carefully and gently, to avoid violent vibration.
(7) After each measurement, the probe should be wiped clean after pulling out, and organize the wire for the next use. Store the grounding resistance test meter in a dry, light-proof and vibration-free place.
Techwin grounding resistance test meter is specially designed for online monitoring of the grounding network resistance of lightning protection devices. It can be installed individually or assembled into a wired network and wireless network system. It can be used for wired or wireless communication. It can be externally powered or equipped with solar power. It is equipped with a standard RS485 interface for data communication and can provide a custom programming interface for customers to interface with other private protocols.
What Are the Classification Protection of Lightning Protection System?January 10, 20221. Type 1 lightning protectionThe aim is to prevent voltage surge from being directly conducted from LPZ0 to LPZ1 and limit the voltage surge varying from tens of thousands of volts to hundreds of tho...view
Understanding the Function and Installation Method of Surge Protection BoxJuly 3, 2024As computer networks become increasingly integrated into people's lives and work, heralding the advent of the digital and information era, the importance of data center rooms and lightning protect...view
How to install a SPD?August 11, 2023Techwin surge protective devices (SPDs) are designed to protect electrical equipment from power surges. Installing an SPD is essential to ensuring the safety and longevity of your devices. Here is a s...view
Maximizing Equipment Lifespan: Power Surge Monitoring for Industrial ApplicationsSeptember 11, 2023In industrial settings, where complex machinery and electronic equipment are the backbone of operations, ensuring the longevity and reliability of these assets is of paramount importance. Industrial e...view
The difference of Type1/Type 1+2 SPD and Type 2 SPDAugust 11, 2023TECHWIN surge protectors offer reliable and efficient protection against power surges and electrical disturbances. Our range of surge protection devices includes Type 1/Type 1+2 and Type 2 SPDs, speci...view
Power Supply Surge Protection for Industrial Control PanelsJuly 3, 2024Power supply surge protection for industrial control panels is not just a recommended practice but an essential legal requirement, a mandatory measure to protect electrical systems. Typical control pa...view