This is the most effective and fundamental direct lightning protection measure, particularly suitable for lightning-prone areas or critical lines.
Principle: One or two well-grounded metal wires (typically galvanized steel strands) are installed atop utility poles above the power lines. During lightning discharge, the ground wire acts as the preferred point of strike, channeling the massive lightning current into the ground through the grounding device, thereby protecting the conductors below from direct lightning hits.
Applicable Scenarios:
Regions with frequent lightning activity (high average annual thunderstorm days).
Lines supplying critical loads requiring high reliability.
Lines passing through hilly or elevated terrain with high soil resistivity.
SPDs are primarily used to limit lightning-induced overvoltages. They serve as a crucial supplement to ground wires and are the main protection method for lines without ground wires.
Principle: SPDs are connected in parallel between the line (phase conductor) and the ground. Under normal operation, they exhibit high impedance and do not affect the system. When a dangerous lightning overvoltage occurs on the line, their impedance rapidly decreases to a low value, instantly diverting the lightning current and limiting the residual voltage to a level tolerable by equipment. This protects line insulators and electrical devices. Afterward, they quickly return to a high-impedance state.
Installation Locations:
Line endpoints: at the substation outlet and the end of the line (before entering user premises).
Critical poles such as branch poles, terminal poles, and angle poles.
Intermediate sections of long lines, installed at regular intervals (e.g., every 200–500 meters).
Entrances to particularly critical users or equipment.
The effectiveness of all lightning protection measures relies on proper grounding. Without adequate grounding, neither ground wires nor surge arresters can function effectively.
Requirements:
The grounding resistance of poles should be as low as possible (typically ≤30Ω, which may be relaxed to ≤50Ω in areas with high soil resistivity).
Grounding down conductors for ground wires and surge arresters must have reliable connections and sufficientcross-sectional area.
Grounding electrodes should be buried in moist soil. If necessary, soil replacement, use of resistance-reducing agents, or increasing the number of grounding electrodes can be employed to lower grounding resistance.
This is an economical and practical method but has certain limitations.
Principle: If structures such as buildings or trees taller than the line exist nearby and their protective zone covers the line, these natural objects can provide a degree of protection.
Note: This method is unreliable, as trees may be cut down, and their high resistance may cause side flashes during lightning strikes, endangering the line. It should not be relied upon as a primary measure.
1. Installation of Arcing Gaps: In some cases, small arcing gaps can be installed in parallel with insulators. During overvoltage events, the gap breaks down first, protecting the insulator from flashover. However, this may cause line tripping and requires coordination with auto-reclosing devices.
2. Use of Porcelain Cross-Arms or Enhanced Insulation: While not preventing direct lightning strikes, this improves the line’s withstand capability, reduces the probability of power arc formation, and lowers the risk of tripping.
3. Operation and Maintenance: Regular inspections to ensure ground wires, surge arresters, and grounding down conductors are well-connected, free from corrosion, and undamaged; periodic measurement of grounding resistance to ensure compliance with requirements.
For direct lightning protection of low-voltage overhead lines, a combined approach is typically adopted:
For critical lines in lightning-intensive areas: Prioritize the "ground wire + robust grounding" method, supplemented with surge arresters at key points.
For general lines: The most economical and practical solution is "multi-point installation of surge arresters + ensuring proper grounding for every pole."
In all cases: Adequate grounding is the cornerstone of all lightning protection measures and must be given high priority.
Precautions for Installing the External Lightning Protection DeviceNovember 9, 20211. Installation of down-conductor and flashover conductor of external lightning protection deviceDown-conductor and lightning conductor should be in the correct position, and the laying should be smoo...view
Intelligent PDU Surge Protector: A Perfect Combination of Efficient Protection and Smart ManagementApril 23, 2025As the widespread use of modern data centers, video surveillance systems, Ethernet switches, and various terminal devices continues, the safety and stability of power equipment have become particularl...view
Excellence in Quality: Product Applications of Photovoltaic DC Power Supply SPDJune 26, 2024Photovoltaic equipment is often exposed to outdoor environments over the long term, while the electronic components of inverters are highly sensitive to environmental conditions. Particularly on the D...view
Lightning Protector: Essential Installation and Maintenance TipsFebruary 29, 2024As unpredictable as weather can be, one thing we can always count on is the presence of lightning during thunderstorms. While its awe-inspiring beauty can be captivating, the power of lightning can al...view
What Is a Surge Circuit Breaker?June 26, 2024Surge Circuit Breaker, also known as SCB, is a new type of product used to replace traditional dedicated circuit breakers or fuses. It is specially designed for surge current protection, addressing th...view
Will a surge protector still work after a power failure? –Comprehensive Technical AnalysisApril 27, 2025Systematic maintenance ensures SPD reliability post-power failure.view