In the lightning protection of a building's power supply, a lightning-proof surge protector safeguards equipment by discharging lightning currents and limiting surge voltages. It is the main means of lightning protection for electronic equipment and an essential part of internal lightning protection. Correct selection and installation of lightning-proof surge protectors can effectively ensure the safety of electrical equipment within buildings. This article will detail the methods for selecting lightning-proof surge protectors.
A surge protector tested for Class I or Class II should be installed at the main distribution box where the AC power line enters the building, at the intersection of the lightning protection zones LPZ0A or LPZ0B and LPZ1, to serve as primary protection.
In the subsequent protection zones at the distribution sub-distribution box, electronic equipment room distribution box, etc., a Class II or Class III surge protector should be chosen for installation based on the equipment's needs as secondary protection. For particularly important electronic information equipment power ports, a Class II or Class III surge protector can be added as fine protection. For information equipment using DC power, choose a compatible DC power surge protector according to its operating voltage requirements.
The number of levels of lightning proof surge protector should comprehensively consider the following factors:
Protection distance
Length of connecting wires for the lightning-proof surge protector
Impulse voltage rating (UW) of the protected equipment
Each level of surge protector should withstand the expected discharge current at the installation point, and its effective protection level (UP/F) should be less than the UW of the corresponding equipment.
When the line length between a voltage-switching type surge protector and a voltage-limiting type surge protector is less than 10 meters, or the line length between voltage-limiting type surge protectors is less than 5 meters, a decoupling device should be installed between the two levels of surge protectors. If the surge protector has an automatic energy coordination function, the line length is not limited.
The connecting wires of a lightning-proof surge protector should be short and straight, with a total length not exceeding 0.5 meters.
When the line length between the primary spd power supply at the entrance and the protected equipment is greater than 10 meters, an additional surge protector should be installed at the sub-distribution box or protected equipment location.
Proper selection of lightning-proof surge protectors requires comprehensive consideration based on the building's lightning risk assessment results, lightning protection zone division, and equipment needs. Reasonably configuring and installing surge protectors can not only extend the service life of the equipment but also ensure the safe operation of the building's electrical system.
Circuit Design of Signal Surge ProtectorSeptember 22, 2022Signal surge protector (SPD) can be divided into telephone signal surge protector, network signal surge protector, control signal surge protector, high-power broadcast signal surge protector, and moni...view
Difference Between Surge Protector and Backup ProtectorApril 26, 2022The special protection device for low-voltage surge protector (SSD) is an external disengagement device of the surge protector used in the low-voltage power supply system, which can withstand the expe...view
Antenna Surge Protective Device for Cellular Base StationsJuly 3, 2024Currently, the world is experiencing significant changes, including planning and establishing new mobile radio sites, as well as revitalizing and expanding existing network infrastructure. In the era ...view
When Do You Need to Install Surge Protection Devices?October 9, 2024Frequent Thunderstorm Areas and Seasonal ProtectionIn regions where thunderstorm activities are frequent, especially during the summer thunderstorm season, it becomes particularly important to install...view
Understanding The Technology Behind Lightning Protection Devices For Building StructuresJanuary 10, 2024In the field of building safety, the technology encompassed within lightning protection devices for building structures serves as a strong shield against the unpredictable nature of lightning. This pa...view
Surge Protector: Guardian of Thunderstorm WeatherMarch 13, 2023During the high-frequency thunderstorm season, the unstable weather brings not only inconvenience to people's travel but also poses potential safety hazards. Lightning waves can be introduced with...view