In the lightning protection of a building's power supply, a lightning-proof surge protector safeguards equipment by discharging lightning currents and limiting surge voltages. It is the main means of lightning protection for electronic equipment and an essential part of internal lightning protection. Correct selection and installation of lightning-proof surge protectors can effectively ensure the safety of electrical equipment within buildings. This article will detail the methods for selecting lightning-proof surge protectors.
A surge protector tested for Class I or Class II should be installed at the main distribution box where the AC power line enters the building, at the intersection of the lightning protection zones LPZ0A or LPZ0B and LPZ1, to serve as primary protection.
In the subsequent protection zones at the distribution sub-distribution box, electronic equipment room distribution box, etc., a Class II or Class III surge protector should be chosen for installation based on the equipment's needs as secondary protection. For particularly important electronic information equipment power ports, a Class II or Class III surge protector can be added as fine protection. For information equipment using DC power, choose a compatible DC power surge protector according to its operating voltage requirements.
The number of levels of lightning proof surge protector should comprehensively consider the following factors:
Protection distance
Length of connecting wires for the lightning-proof surge protector
Impulse voltage rating (UW) of the protected equipment
Each level of surge protector should withstand the expected discharge current at the installation point, and its effective protection level (UP/F) should be less than the UW of the corresponding equipment.
When the line length between a voltage-switching type surge protector and a voltage-limiting type surge protector is less than 10 meters, or the line length between voltage-limiting type surge protectors is less than 5 meters, a decoupling device should be installed between the two levels of surge protectors. If the surge protector has an automatic energy coordination function, the line length is not limited.
The connecting wires of a lightning-proof surge protector should be short and straight, with a total length not exceeding 0.5 meters.
When the line length between the primary spd power supply at the entrance and the protected equipment is greater than 10 meters, an additional surge protector should be installed at the sub-distribution box or protected equipment location.
Proper selection of lightning-proof surge protectors requires comprehensive consideration based on the building's lightning risk assessment results, lightning protection zone division, and equipment needs. Reasonably configuring and installing surge protectors can not only extend the service life of the equipment but also ensure the safe operation of the building's electrical system.
What Is a Surge Circuit Breaker?June 26, 2024Surge Circuit Breaker, also known as SCB, is a new type of product used to replace traditional dedicated circuit breakers or fuses. It is specially designed for surge current protection, addressing th...view
How to Choose the SPD for Solar?June 26, 2024Are you worried that expensive photovoltaic solar systems might be damaged by voltage spikes? The reality is that without surge protection, even the slightest voltage spike can damage your solar panel...view
Antenna Surge Protective Device for Cellular Base StationsJuly 3, 2024Currently, the world is experiencing significant changes, including planning and establishing new mobile radio sites, as well as revitalizing and expanding existing network infrastructure. In the era ...view
What Are the Experimental Requirements for the Leakage Current of the Surge Protector?August 10, 20221. The value of surge protector discharge current protection equipmentIn addition to the discharge current, the lightning protection capability also depends on the test waveform. The outdoor incoming ...view
What if the Connecting Wire of the Lightning Surge Protector is Too Long?November 9, 2021In lightning protection engineering, when arranging surge protectors, the connecting wires are required to be short and straight. However, in many cases at the construction site, the connecting wires ...view
Technical terminology in IEC61643 standards-1December 8, 20212.1 Technical Term2.1.1. Lightning electromagnetic impulse (LEMP)It is a source of interference. Refers to the effect caused by lightning directly hitting the lightning protection device of a building...view