In addition to the discharge current, the lightning protection capability also depends on the test waveform. The outdoor incoming cabinet uses a Class 1 surge protector, and the lightning current waveform is (10/350μs). According to the highest protection standard (explosive environment), the total lightning The current is only 200KA. The biggest risk to the power distribution system is that each line flows through 25KA. For the base station, even if it is designed according to Category 2, the discharge current of each line is 20KA, which meets the protection requirements. The largest 100kA, 200kA, 400kA (8/20μs) products on the market use varistors and diodes that can only be used as Class 2 surge protectors and cannot pass the Class 1 test, which means they cannot be used for outdoor incoming lines The protection of the cabinet, and the maximum discharge current claimed by such products is 100kA, 200kA, 400kA (8/20μs), which is realized by multiple discharge devices in parallel. action and burn. Furthermore, the meaning of the maximum surge protection capability is that it will be damaged after one hit, which cannot be used as the main parameter in the standard.
The leakage current test is an important item in the detection of industrial surge protectors. According to the technical specifications, the test requirements are listed as follows:
(1) The test is only applicable to SPDs with metal oxide varistor (MOV) as the voltage limiting element and no other series-parallel elements.
(2) The leakage current value of the SPD can be measured with a lightning protection component tester or a leakage current test meter.
(3) First, disconnect the backup protection device and confirm that the power supply is disconnected, then directly measure the corresponding module with the instrument, or remove the pluggable SPD from the line for measurement.
(4) Qualification judgment basis: When measuring 1ma for the first time, the measured value of the leakage current of the SPD composed of a single MOV should not exceed the nominal maximum value of the manufacturer; if the leakage current is not declared by the manufacturer, the measured value should not be greater than 20μA. For a surge protector with multiple MOVs connected in parallel, the measured leakage current should not exceed the maximum nominal value of the manufacturer. If the manufacturer declares the leakage current, the measured value should not be greater than 20μA multiplied by the number of MOV valves. When the number of valves cannot be determined, the measured value of the surge protector should not be greater than 20μA.
(5) When the subsequent measurement is 1ma, the measured value of the leakage current of the surge protector composed of a single MOV and multiple MOVs should not be greater than 1 times the first measured value.
Techwin Supports Nanchang Metro: Safeguarding Urban Traffic SafetyOctober 10, 2025At 10:18 AM on June 28, initial operations simultaneously commenced for three extended lines of Nanchang Metro: the north extension and east extension of Line 1, and the east extension of Line 2. The ...view
Introduction to Signal Surge Protector and Its Lightning Protection FunctionMarch 4, 2022A signal surge protector is a type of surge protection devices that is linked in series on a signal line to reduce transient over-voltages and deflect surge currents away from the signal line. Signal ...view
The Difference Between Surge Protector and Lightning ArresterFebruary 17, 2023Lightning arresters and surge protective devices, as commonly used components in electrical equipment, have the function of preventing overvoltage, especially lightning overvoltage, but there are stil...view
The Principle of Surge Protector Lightning ProtectionSeptember 18, 2021The energy of lightning is huge, and lightning strikes can lead to casualties and property damage. With the development of technology, mankind has developed many lightning protection products to prote...view
What Are the Effects of Surge Protectors?April 26, 2022SPD surge protection device is an electrical equipment used to limit transient overvoltage and discharge surge current. It is also called lightning arrester, which is an important part of the internal...view
Benefits of Using Signal Surge ProtectorsFebruary 29, 2024In today's fast-paced world, we rely heavily on technology to stay connected, informed, and productive. From smartphones to laptops to smart TVs, we are constantly surrounded by electronic devices...view