When the power distribution system is struck by lightning and when switching on or off inductive loads or large loads, it often produces high operating overvoltages, also called surge voltages. Surges on the lines can cause damage to the circuits and components of electronic equipment. Failure, burn out equipment components.
Our power supply line and equipment grounding line are the two ports where the equipment is most likely to introduce lightning surge pulses. It is a common practice that we care about installing surge protectors on equipment access lines. When our grounding is not good, because the ground resistance is too large, the residual voltage of the discharged lightning is too high, and the high ground potential counterattack enters the equipment through the grounding wire, causing damage to the signal network equipment.

IF: IE=10kA (10/350μs), RB=20Ω
Uf=IE×RB=10*20=200kV;
The 200kV residual voltage enters the weak current and signal protection ground of the communication network through the shared grounding system, causing communication interruption and other faults.
Therefore, we take advantage of the high impedance characteristics of the ground flashback protection device against lightning surge pulses to force the lightning surge pulse to be discharged into the grounding device through the bleeder unit. At the same time, the ground flashback protection device prevents the high ground potential counterattack from entering the signal network equipment, effectively preventing energy Through the low voltage working ground and signal protection ground, the low voltage and weak current signal lines can be entered, so that the grounding resistance value of the protected system to the ground can be relaxed, and the protection requirements can be met by simple grounding (such as the building foundation steel bar as a grounding device) .
By installing the ground flashback spd protection device, the ground potential counter-strike shunt can be reduced to less than 5% of the original counter-strike current, effectively solving the harm caused by the lightning surge pulse when the grounding state is poor. At the same time, it can be used with surge protectors of lightning protection products to effectively reduce the lightning residual voltage and residuals of the protected equipment, thereby protecting the equipment.

IF: IE=10kA (10/350μs) RB=40Ω IR%=3%
IR=10*3%=300A
Uf=IE×RB=10*40*3%=12kV;
The installation of lightning counterattack protection device can reduce the amplitude of counterattack voltage and current to 3-5% of the original value, which greatly protects the line equipment.
Remarks: Simply grounding is required, and grounding is also required. Completely ungrounded neither meets the requirements of various electrical codes, nor can it meet the conditions of use of this product. Will not play a protective effect.
The Position of Installing Surge ProtectorMarch 23, 20221. Where to install surge protector?The position of the surge protector: the surge protector is an important component of the lightning protection project in a building, so the location of the surge prote...view
Debunking Common Myths and Misconceptions about Lightning Protection DevicesFebruary 29, 2024In today's fast-paced world, technology plays a crucial role in our everyday lives. From smartphones to smart homes, we rely on various electronic devices to stay connected and entertained. Howeve...view
View of beautiful waterfall in Maluan Mountain in autumnOctober 21, 2022In order to enrich the cultural life of employees, under the organization of the Administration Department, We established "Techwin Outdoor Activities Team" mean to our employees to w...view
How Important is Installing Camera Signal Surge Protectors?March 13, 2023Network camera lightning protector, network camera lightning protection, camera lightning protector, KAIYUAN network camera, surge protector suitable for AC/DC power supply and network interface monit...view
What if the Connecting Wire of the Lightning Surge Protector is Too Long?November 9, 2021In lightning protection engineering, when arranging surge protectors, the connecting wires are required to be short and straight. However, in many cases at the construction site, the connecting wires ...view
Power Supply Surge Protection for Industrial Control PanelsJuly 3, 2024Power supply surge protection for industrial control panels is not just a recommended practice but an essential legal requirement, a mandatory measure to protect electrical systems. Typical control pa...view