(1) The voltage protection level Up of SPD should always be less than the impulse withstand voltage Uc of the protected equipment, and greater than the maximum operating voltage Us of the power grid obtained according to the grounding type, that is, Us<Up<Uc. If the line is not shielded, it should be taken into account the line induced voltage, Uc should be considered as 80% of its value.
(2) The leads at both ends of the surge protector SPD and the protected equipment should be as short as possible and controlled within 0.5m.
(3) If the Up of the incoming SPD plus the induced voltage of the leads at both ends and the reflected wave effect are too high compared with the impulse withstand voltage of the protected equipment farther away from it, it needs to be added at this equipment. When the second-level SPD is installed, its nominal discharge current In should not be less than 8/20μs 3kA; when the incoming SPD is not more than 10m away from the protected equipment, if the SPD's Up plus the induced voltage of the leads at both ends is less than the equipment's 80% of Uc, in general, SPD may not be installed at the device.
(4) When there is a switchboard between the SPDs installed according to the requirements of point 3 above, if the Up of the first-level SPD plus the induced voltage of the leads at both ends cannot protect the equipment in the switchboard, it should be installed in the switchboard. The second-level SPD, its nominal discharge current In should not be less than 8/20μs 5kA.
(5) When multiple SPDs are installed on the line, the line length between the voltage switching SPD and the voltage limiting SPD should not be less than 10m, and the line length between the voltage limiting SPD should not be less than 5m. For example, the protected equipment is relatively close to the power distribution center, and more wires can be deliberately wound in the line laying.
(6) When the distance between the surge protector SPD at the incoming end and the protected equipment is greater than 30m, another SPD should be installed as close as possible to the protected equipment, and the current capacity can be 8kA.
(7) When selecting SPD, care should be taken to ensure that the SPD will not be burned due to power frequency overvoltage, because SPD is anti-transient overvoltage, power frequency overvoltage is transient overvoltage (ms level), and the energy of power frequency overvoltage is Hundreds of times the transient overvoltage energy, therefore, care should be taken to select an SPD with a higher power frequency operating voltage.
(8) Protection of SPD: each level of SPD should be protected, or fuses can be used for protection, and the breaking capacity of the surge protector is greater than the maximum short-circuit current at the place.
(9) In addition, when selecting SPD, attention should also be paid to: the response time is as fast as possible; the length of service life, the price factor, the maintainability, the size of the flow capacity, and the humidity resistance.
Power Surge Monitoring Device: Intelligent Monitoring and Power ProtectionOctober 9, 2024In modern life, electricity has become the cornerstone of our daily life and work. However, with the increasing complexity of the power network and the presence of unforeseen factors such as lightning...view
View of beautiful waterfall in Maluan Mountain in autumnOctober 21, 2022In order to enrich the cultural life of employees, under the organization of the Administration Department, We established "Techwin Outdoor Activities Team" mean to our employees to w...view
The Meanings of Uc and Up on AC Power SPD and How to ChooseJuly 3, 2024Power surge protectors, also known as power lightning protectors, are suitable for AC 50/60Hz power supply systems and can protect the power systems of residential homes, tertiary industries, and indu...view
Use, Installation and Configuration of Surge ProtectorsMay 20, 20221. Parameters selected by SPD of surge protector at all level1. SPD-1If the first-level surge protector SPD1 is installed in the general power distribution room of a building, three switch-type surge ...view
A Lightning Surge Protection Plan Required for Petrochemical ProjectsNovember 28, 2023Implementing a lightning surge protection plan is crucial for petrochemical projects to safeguard critical infrastructure, equipment, and personnel. Lightning poses a significant risk to facilities, e...view
Protecting Your Communication Network: The Role of Antenna Feeder ArrestersSeptember 11, 2023In today's interconnected world, our reliance on communication networks is undeniable. Whether it's for business operations, emergency services, or staying connected with loved ones, these net...view